HBP Series

 

A centrifugal blower and high efficiency heater elliminates the use of valuable compressed air to be used for desiccant regeneration. The completely automatic drying system uses blower to pull ambient Air and pass it through the heater. This hot Air stream flows opposite to drying flow direction. Hot Air above 200 oF regenerates the moisture inside desiccant bed and strips it completely of all moisture. The advanced control system monitors the dew point and adjusts the heating / regeneration accordingly thereby providing valuable energy savings. The heater circuit is completely insulated ensuring maximum heating efficiency.

Technical specifications

  • Dew point monitoring and control
  • Computer Control
  • Display Status
  • Display Alarms
  • Display Pressure
  • Remote Start / Stop
  • Low Pressure Alarm
  • Minimum Pressure monitoring valve
  • High pressure switches and alarms
  • Externally heated or heatless dryer functions integrated to the HBP dryer
 

Description

GENERAL INFORMATION

HBP Series

HBP 850 / 1000 / 1250 / 1500 / 1800 / 2200 / 2700 / 3200 / 3600 / 4400 / 5000 / 6300 / 7200 / 8800 / 10800

Principle of Operations

A centrifugal blower and high efficiency heater elliminates the use of valuable compressed air to be used for desiccant regeneration. The completely automatic drying system uses blower to pull ambient Air and pass it through the heater. This hot Air stream flows opposite to drying flow direction. Hot Air above 200 oC regenerates the moisture inside desiccant bed and strips it completely of all moisture. The advanced control system monitors the dew point and adjusts the heating / regeneration accordingly thereby providing valuable energy savings. The heater circuit is completely insulated ensuring maximum heating efficiency.

  •  Dew point monitoring and control
  •  Computer Control
  •  Display Status
  •  Display Alarms
  •  Display Pressure
  •  Remote Start / Stop
  •  Low Pressure Alarm
  •  Minimum Pressure monitoring valve
  •  High pressure switches and alarms

Externally heated or heatless dryer functions integrated to the HBP dryer

Normal Working Conditions

  •  7 bar Inlet Pressure 35 oC Inlet Temperature
  •  100 % Inlet Air rel. humudity
  •  Nominal pressure dew point is
  •  40 oC / Maximum working pressure 12 bar (g)

PLC is standard

HBP Blower Purge Dryers has a very reliable electronic controller makes sure that the dryer operates perfectly all through the servicelife of the dryer. Touch screen PLC is capable of showing the cycles as well as the valves which operate on real time. It also shows the dew point (if applicable).

User friendly multi-langual PLC helps the end users understand the operation system any field issues easily.

Activated Alumina

Hertz uses a mixture of adsorption media in its heatless range of desiccant dryers to achieve consistent dewpoint. Activated Alumina, Molecular Sieve and Silica Gel are used in varying ratios depending on the application.

MODELS AND TECHNICAL INFORMATION

ModelCapacity*Connection SizeVoltage** Maximum working PressureMaximum ambient TemperatureMaximum Inlet TemperatureIncluded Filter Dimensions (mm)Weight
m3/mincfmbar0C0Cand TypeLengthWidthHeightKg
HBP 85014.2500G 2"400V/3/50Hz104045HGKO 851 MX+MY+MP(H)129611802299C/F
HBP 100016.7589G 2"400V/3/50Hz104045HGKO 1210 MX+MY+MP(H)120013102415C/F
HBP 125020.8736DN80400V/3/50Hz104045HGKO 1820 MX+MY+MP(H)161012702468C/F
HBP 150025883DN80400V/3/50Hz104045HGKO 1820 MX+MY+MP(H)161012702563C/F
HBP 1800301059DN80400V/3/50Hz104045HGKO 1820 MX+MY+MP(H)156315152479C/F
HBP 220036.71295DN80400V/3/50Hz104045HGKO 2220 MX+MY+MP(H)156314552789C/F
HBP 2700451589DN80400V/3/50Hz104045HGKO 2700 MX+MY+MP(H)161515142836C/F
HBP 320053.31883DN100400V/3/50Hz104045HF 3200 MX+MY+MP(H)171016603054C/F
HBP 3600602119DN100400V/3/50Hz104045HF 4300 MX+MY+MP(H)171016603268C/F
HBP 440073.32590DN100400V/3/50Hz104045HF 4300 MX+MY+MP(H)197524922910C/F
HBP 500083.32943DN125400V/3/50Hz104045HF 6500 MX+MY+MP(H)204525603382C/F
HBP 63001053708DN150400V/3/50Hz104045HF 6500 MX+MY+MP(H)209029633328C/F
HBP 72001204238DN150400V/3/50Hz104045HF 8500 MX+MY+MP(H)202033633047C/F
HBP 8800146.75179DN150400V/3/50Hz104045HF 8500 MX+MY+MP(H)202033633341C/F
HBP 108001806357DN200400V/3/50Hz104045HF 11000 MX+MY+MP(H)249234813765C/F